MPC-Net Control Panel Networking

FEATURES

  • 127 nodes with total capacity of over 100,000 points True peer-to-peer communications with each node storing it’s own program and easily communicating it’s status to the network
    True distributed intelligence
    NIB module connect MPC-6000 & MPC-7000 panels anywhere on the network
    No “Master Node” necessary
    Each node acts as a repeater to regenerate data signals
    Each node is electrically isolated
    Failure of one node does not affect the operation or communication of other nodes on the network
    NFPA style “4” or style “7” network operation
    It is possible to install multiple Network Annunciator Units (RNDs) anywhere on the network
    Alarm silence, acknowledge and panel reset controls are programmable at each Network Annunciator
    MPC-Net network computers with graphic software (CADGraphics) will provide detailed annunciation or instruction via computer interface
    UL, CSFM and MEA Listed
  • Nodes may be connected using category 5 or fiber optic cable

DESCRIPTION
Faraday’s MPC-Net™ Control Panel Networking will allow Faraday MPC-6000 & 7000 Series Intelligent Fire Alarm Control Panels to form a network. Each local control panel (node) maintains it’s own area of protection, while monitoring and controlling other network nodes. Local information is displayed at each network node. Central annunciation and control can be attained by mounting a remote network display (RND-1) or CADGraphics at an area such as a security desk.

The Faraday MPC-Net is an RS-485 based network that allows a maximum of 127 nodes with a total capacity of over 100,000 points. Since installation and programming of the MPC-6000 and MPC-7000 Fire Alarm Control Panels is easily accomplished, the configuration of the MPC-Net is simple, yet powerful.

Network Computer/CADGraphics
(12533P/G/S) or 12534P/G/S)
The network computer is a UL 864 listed desktop computer with the CADGraphics software installed. The network computer comes with either a 19" monitor or a 19" touch screen monitor. CADGraphics is a graphical program designed to annunciate activity on the network. There are three versions available; Silver, Gold and Platinum. It has the ability to show floor plans with device placement, descriptive written, and audible messages that can be unique to every initiating device on the network. The software is loaded on a UL 864 listed computer, running Windows NT 4.0. Requires a (12526A) NIB-I board

NIB - Network Interface Board
(12523A,12526A or 12603A)
The Faraday MPC-Net network is a way to link Faraday MPC-6000 and MPC-7000 Fire Alarm Control units , RND-1 Remote Network Annunciators, and devices such as printers, and computers together to form a peer-to-peer network. Each device connected to the network requires a NIB (network interface board). The NIB communicates with the attached device though an RS232 port. It receives 24VDC from a MPC-6000, MPC-7000 or RND-1. The network is wired from node to node in a daisy chained ring configuration for style 7 operation. It can also be wired node to node in a daisy chained “flat” configuration with two ends for style 4 operation. (Style 7 is recommended). The network side of the NIB has 2 ports. Port 1 (reverse direction) is an isolated port and port 2 (forward direction) is a non-isolated port. Port 2 of a NIB must be wired to port 1 of the next NIB (see wiring dia-grams). The signals are regenerated at each NIB allowing a distance of 3000 feet between NIBs. A total of 127 NIBs (note: address 121- 127 are reserved for certain devices) can be connected on a network.
There are three versions of NIBs:

  1. P/N 12523A is a NIB designed to connect to an RND-1, MPC-6000 and MPC-7000 (mounts externally) to the MPC-Net. P/N 12526A is a NIB with an isolated RS232 port. It is designed to connect printers and computers to the MPC-Net. The computer may be used as a terminal or to run the CADGraphics software.
  2. P/N 12603A is a NIB designed to connect the MPC-6000 and MPC-7000 to the MPC-NET and mounts inside the enclosure of either the MPC-6000 or MPC-7000. 12523A’s mount in a 6 gang box supplied by others or a (12411014) surface back box.

Fiber Optic Converters
It is possible to convert one or both of the network ports of an “A” version NIB to use fiber media instead of Category 5 wire with the use of optional fiber converters 12535 or 12536. Each converter converts one port of the NIB to fiber media. There is a converter for single mode fiber and one for multi-mode fiber. The converters plug directly into sockets onto the NIBs. Different media types can be mixed on the same NIB. A maximum of 2 media types can be used per NIB.

The 12535 & 12536 Fiber Optic Converters allow nodes to be connected via Fiber Optic Cable. The multi-mode converter 12535 is designed to use duplex 62.5/125 µm multi-mode fiber cable with ST connectors. The single mode converter 12536 is designed to use duplex 9/125 µm single mode fiber cable with SC connectors. The maximum loss allowed between each NIB with fiber converters is 10dB

RND-1 Network Annunciator (12529)
The RND-1 is designed to annunciate network events (alarms, troubles and supervisories). It is capable of scrolling through network events. These events can be acknowledged either globally or for the RND-1 only. Alarms may also be silenced globally. There is also the ability to reset all panels on the network or just the RND-1. There is also a network event history that can be retrieved.The RND-1 can log on to any panel on the network. At that point, access to user and maintenance levels for that panel are available at the RND-1.

Up to 16 RDC-2 remote annunciators can be slaved off of one RND-1. The RDC-2 duplicates the display and control functions of the RND-1. The RND-1 requires a (12523A) NIB board.

Line Surge Suppressor (12525)
The 12525 is a data line surge suppressor and is required when networking from building to building. The surge suppressor comes mounted in a surface backbox and can be used with a NIB for mounting.

APPLICATIONS

  • Campus settings Large multiple building complexes Hospitals Industrial buildings and facilities
  • High rise buildings

ENGINEERING SPECIFICATIONS
It shall be possible, by adding a NIB, to place a MPC-6000 or MPC-7000 panel into a network (Faraday MPC-Net) consisting of other MPC-6000 or MPC-7000 Fire Alarm Panels. The NIB shall provide a means for the control panel to be addressed as a “node” on and communicate with the Faraday MPC-Net.

 